Brand/ Manufacturer:
General ElectricDimensions:
2.9 cm x 13.0 cm x 12.4 cmWeight:
0.1kgCountry of Origin: :
United StatesDescription:
Universal Analog Input Module
Mfr. Part Number: |
IC695ALG600 |
|
|
Manufacturer: |
General Electric |
|
|
Description: |
The IC695ALG600 is an 8-Channel, Thermocouple, Resistance, Current/Voltage, RTD, Universal, Analog Input module from the GE Fanuc RX3i Series. The IC695ALG600 provides 8 general purpose input channels and 2 Cold Junction Compensation (CJC) channels |
Contact Details: |
E-mail:plcsale@mooreplc.com Skype:dddemi33 Whatsapp/Wechat:+86 18030235313 Manager: Tiffany
|
|
|
Status: |
Hope we can do more business soon ! There will become your honest cooperation partners!
Manufacturer |
GE Fanuc |
Series |
Versamax |
Part Number |
IC695ALG600 |
Product Type |
Thermocouple Input Module |
Number of Channels |
8 |
Input Resolution |
11 to 16 bits |
Power Dissipation |
5.4 Watts |
Backplane Power Requirement |
400 mA at 5V, 350 mA at 3.3V |
RTD Cable Impedance |
25 Ohms |
RTD Wire Length |
1000 feet |
Open circuit detection time |
5 seconds max. Open circuit detection is available for all configurations except +/- 20mA current, 0-20mA current, and +/-10V voltage. |
Max Overvoltage |
+/-14.5VDC continuous |
Max Overcurrent |
28 mA continuous |
Normal Mode Noise Rejection |
95 dB minimum @ 50/60 Hz with 8 Hz filter 85 dB minimum @ 50/60 Hz with 12 Hz filter |
Common Mode Noise Rejection |
120dB minimum @ 50/60 Hz with 8 Hz filter 110dB minimum @ 50/60 Hz with 12 Hz filter |
Settling time to 5% of Full Scale (notch filter dependent) |
<80 mS |
Calibrated Accuracy at 25°C |
Better than 0.1% of range (except 10 ohm CU RTD) Accuracy depends on A/D filter, data format, input noise, and ambient temperature. |
Calibration interval |
12 months typical to meet accuracy specifications over time. Module will allow for user offset to be applied as a periodic calibration adjustment. |
Input Offset Drift with Temperature |
3.0 milliohm/°C maximum 2.0 uV/°C maximum |
Gain Drift with Temperature |
50 ppm/°C typical (90 ppm/°C maximum) |
Module error over Full Temp range |
0.5% of range typical (depends on range) 1.0% of range maximum |
Module Scan Time (notch filter dependent) |
(Assumes 2 ADC’s running in parallel, no CJC or lead resistance) 10 ms per Channel × 4 Channels = 40 ms (1K Hz filter) 127 ms per Channel × 4 Channels = 508 ms (8 Hz filter) Channels that are disabled are not scanned, shortening scan time. |
Module conversion method |
Sigma-delta |
Isolation Voltage channel to channel group to group terminal block to backplane/chassis |
Opto-isolated, transformer isolated +-12.5Vdc channel to channel Tc/V/I/RTD 250 VAC continuous/1500 VAC for 60 seconds 250 VAC continuous/1500 VAC for 60 seconds |
Picture/ Video Request
It's like having the store come to you!
Quick Quotes :
Receive price & availability FAST from our dedicated customer service team.Delivery :
Expedited, Freight, and International shipping available.
Warranty :
If there's a problem, we'll make it right. Your satisfaction is how we measure success!Returns :
No hassle return policy.Repair :
Our team of engineers are creative problem solvers who understand your challenges.Payment :
Custom Calibration :
You give us the specs and we do the rest.Share this page :
Tweet
Share
Share
Email Us