Part number VE4005S2B3 is listed by Emerson as 8-Channel 4-20 mA HART Analog Output with 16-Pin Mass Termination Block.
Item NO.:
VE4005S2B3Brand/ Manufacturer:
EmersonDimensions:
8-Channel 4-20 mA HART Analog Output with 16-Pin Mass Termination BlockWeight:
Not stated in the current official product data sheetCountry of Origin: :
Not stated in the current official product data sheetDescription:
Verify the 16-pin mass-termination cable assembly, loop burden, 24 V field supply and HART requirements as one engineered circuit.8-Channel 4-20 mA HART Analog Output with 16-Pin Mass Termination Block. Verify the 16-pin mass-termination cable assembly, loop burden, 24 V field supply and HART requirements as one engineered circuit.
Installation planning
Confirm VE4005S2B3 protection, enclosure airflow, mounting arrangement and operating temperature before installation.
Storage and handling
Protect VE4005S2B3 from impact, contamination, moisture and electrostatic discharge before installation.
Send the full part number, required quantity and destination. Request current photos, approval markings and connector details before ordering.
Part number VE4005S2B3 is listed by Emerson as 8-Channel 4-20 mA HART Analog Output with 16-Pin Mass Termination Block.
VE4005S2B3 belongs to the Emerson DeltaV M-series Traditional I/O hardware family. Its exact ordering suffix defines the electrical function and termination arrangement; selection must be based on the full model, not on physical appearance alone.
Purchasing check: Lifecycle status is separate from exact product identification. Confirm current orderability, supported hardware revision, condition and lead time with Emerson or the sales team.
Important: Approve replacements only after the full model, hardware revision, carrier or termination arrangement, field power and site requirements have been checked.
Use the following checks to confirm that the exact VE4005S2B3 configuration fits the installed DeltaV system.
Verify the 16-pin mass-termination cable assembly, loop burden, 24 V field supply and HART requirements as one engineered circuit.
Technical basis: Emerson DeltaV M-series Traditional I/O Product Data Sheet, March 2026
It is the eight-channel 4-20 mA HART analog-output configuration with a 16-pin mass termination block.
The nominal range is 4-20 mA and the documented full signal range is 1-23 mA.
The B3 suffix identifies the 16-pin mass termination block; verify the complete mass-termination cable and remote termination pinout.
Emerson specifies 20 mA with a 21.6 V DC supply into a 700 Ω load; calculate the complete loop burden before commissioning.
Yes, the associated eight-channel AO card is a 4-20 mA HART interface; confirm the configured channel and field-device compatibility.
The AO-card specification lists 0.25% of span over the temperature range with 12-bit resolution.
Use 100 mA typical and 150 mA maximum LocalBus current, plus up to 300 mA field-circuit power at 24 V DC ±10%.
Only after checking the wiring architecture. B1 and B3 use different termination arrangements even when associated with the same AO card family.
Verify cable continuity and pinout, loop polarity, field supply, burden, grounding and HART communication on the intended channels.
Request the VE code, card and terminal-block labels, 16-pin connector, cable labels and revision markings in the same photo set.
Only Emerson official documents are linked below. Use the current data sheet for engineering and ordering; use the archived edition only to compare legacy installed hardware.
March 2026 · Current ordering information, supported I/O functions, terminal-block options, environmental limits and engineering data.
OPEN EMERSON PDF → OFFICIAL PDFFebruary 2016 · Legacy ordering tables and historical installation information for comparison with installed hardware.
OPEN EMERSON PDF →Ask for current product photos, the complete nameplate, connectors, packaging and a live or recorded inspection video where available. Verify that the supplied unit carries the exact VE4005S2B3 code and matches the required 8-Channel HART Analog Output with 16-Pin Mass Termination.
| Ordering configuration | 8-channel 4-20 mA HART analog output with 16-pin mass termination block |
|---|---|
| Channels | 8 |
| Nominal signal range | 4 to 20 mA |
| Full signal range | 1 to 23 mA |
| Isolation | Each channel optically isolated from system; factory tested to 1500 V DC |
| Accuracy over temperature | 0.25% of span |
| Resolution | 12-bit |
| LocalBus current | 100 mA typical; 150 mA maximum |
| Field circuit power | 300 mA maximum at 24 V DC ±10% |
| Output compliance | 20 mA at 21.6 V DC supply into 700 Ω load |
| Operating temperature | -40 to 70 °C (-40 to 158 °F) |
| Storage temperature | -40 to 85 °C (-40 to 185 °F) |
| Relative humidity | 5 to 95%, non-condensing |
| Protection rating | IP20 |
| Corrosion protection | ISA-S71.04-1985 Class G3; conformal coating |
| Dimensions | 10.7 × 4.1 × 10.5 cm (H × W × D) |
Tiffany-supported product directory · 24 unique links
Six distinct industrial automation products with Tiffany contact support.
Six distinct industrial automation products with Tiffany contact support.
Six distinct industrial automation products with Tiffany contact support.
Six distinct industrial automation products with Tiffany contact support.
Send the full VE4005S2B3 code, required quantity and delivery country. Our team can check current availability and arrange nameplate photos, packaging images or live/recorded video verification where available.
Confirm the full model, available quantity, condition and estimated dispatch time.
Check the exact model, hardware revision, terminal or carrier arrangement and visible product condition.
Receive quotation, warranty terms, delivery options and international shipping support.
Send the full model, quantity and destination for quotation and availability checking.
Moore Automation kept the VE4005S2B3 quotation concise and ensured the exact output-interface configuration remained clear.
Tiffany worked through the VE4005S2B3 inquiry patiently and clarified the termination details that engineering needed to verify.