Brand/ Manufacturer:
General ElectricDimensions:
6.8x13.1cmx13.5cmWeight:
0.65 kgCountry of Origin: :
United StatesDescription:
Electric Field Control Analog Module
Mfr. Part Number: |
HE670ADC840 |
|
|
Manufacturer: |
General Electric |
|
|
Description: |
The HE670ADC840 provides eight analog channels with a resolution of 12-bits
|
|
|
Contact Details: |
E-mail:plcsale@mooreplc.com Skype:dddemi33 Whatsapp/Wechat:+86 18030235313 Manager: Tiffany
|
|
|
Status: |
Hope we can do more business soon ! There will become your honest cooperation partners!
Isolation levels are 400VDC (channel-to-channel) and 1,000VDC (channel-to-ground). The module changes the current input signals into digital values, which can be accessed through communications with the Bus Interface Unit.
These modules are protected within the standard Field Control I/O case and are compatible with a variety of I/O bases providing flexible termination options.
Technical Specifications
Power Consumption 130mA from backplane
Number of channels 8
Range 4-20mA
Channel-to-Channel Isolation 400VDC
Channel-to-Bus Isolation 1,000VDC
Input Impedance 100 ohms
Output Format Set by BIU
Resolution 12-bits
Maximum error at 25°C ± 1% Full Scale
Operating Temperature 0 to 75°C
Relative Humidity 5% to 95%, non-condensing
Input Power Required Supplied by BIU
Open circuit detection time |
5 seconds max. Open circuit detection is available for all configurations except +/- 20mA current, 0-20mA current, and +/-10V voltage. |
Max Overvoltage |
+/-14.5VDC continuous |
Max Overcurrent |
28 mA continuous |
Normal Mode Noise Rejection |
95 dB minimum @ 50/60 Hz with 8 Hz filter 85 dB minimum @ 50/60 Hz with 12 Hz filter |
Common Mode Noise Rejection |
120dB minimum @ 50/60 Hz with 8 Hz filter 110dB minimum @ 50/60 Hz with 12 Hz filter |
Settling time to 5% of Full Scale (notch filter dependent) |
<80 mS |
Calibrated Accuracy at 25°C |
Better than 0.1% of range (except 10 ohm CU RTD) Accuracy depends on A/D filter, data format, input noise, and ambient temperature. |
Calibration interval |
12 months typical to meet accuracy specifications over time. Module will allow for user offset to be applied as a periodic calibration adjustment. |
Input Offset Drift with Temperature |
3.0 milliohm/°C maximum 2.0 uV/°C maximum |
Gain Drift with Temperature |
50 ppm/°C typical (90 ppm/°C maximum) |
Module error over Full Temp range |
0.5% of range typical (depends on range) 1.0% of range maximum |
Module Scan Time (notch filter dependent) |
(Assumes 2 ADC’s running in parallel, no CJC or lead resistance) 10 ms per Channel × 4 Channels = 40 ms (1K Hz filter) 127 ms per Channel × 4 Channels = 508 ms (8 Hz filter) Channels that are disabled are not scanned, shortening scan time. |
Module conversion method |
Sigma-delta |
Isolation Voltage channel to channel group to group terminal block to backplane/chassis |
Opto-isolated, transformer isolated +-12.5Vdc channel to channel Tc/V/I/RTD 250 VAC continuous/1500 VAC for 60 seconds 250 VAC continuous/1500 VAC for 60 seconds |