Brand/ Manufacturer:
General ElectricDimensions:
3.5x13x13.5cmWeight:
0.3kgCountry of Origin: :
United StatesDescription:
Output Module
Mfr. Part Number: |
IC693MDL742J |
|
|
Manufacturer: |
General Electric |
|
|
Description: |
The IC693MDL742 is a 12/24 volt DC Positive Logic 1 Amp Electronic Short Circuit Protection (ESCP) Output module for the GE Fanuc Series 90-30 |
Contact Details: |
E-mail:plcsale@mooreplc.com Skype:dddemi33 Whatsapp/Wechat:+86 18030235313 Manager: Tiffany
|
|
|
Status: |
Hope we can do more business soon ! There will become your honest cooperation partners!
Technical Specifications
Rated Voltage: 12/24 volts DC
# of Outputs: 16
Freq: n/a
Output Current: 1.0 A per point
Output Voltage Range: 12 to 24 volts DC (+20%, -15%)
DC Power: Yes
The GE Fanuc IC693MDL742 is a 12/24 volt DC Positive Logic 1 Amp Electronic Short Circuit Protection (ESCP) Output module. Made to work with the Series 90-30 PLC, this ESCPP module has a total of 16 output points. These points are arranged in two individual banks of eight. There is a common power output terminal shared by the points of each group. By design, this output module has positive logic characteristics. This means it sources current from either the user common or else the positive power bus, directing it to the load.
Among the load devices that are compatible with the output characteristics of this module are solenoids, indicators and motor starters. Output devices like these must be connected between the negative power bus and the module output. The user must supply external power to operate the field devices. On top of the ESCP module there are two rows of LED indicators. These show the ON/OFF status of each one of the output points. Each green LED corresponds to the relative output point. Row A1 has the LED indicators for outpoints points 1 to 8, while row B1 is for output points 9 to 16.
Rated Voltage |
12/24 volts DC |
Output Voltage Range |
12 to 24 volts DC (+20%, –15%) |
Outputs per Module |
16 (two groups of eight outputs each) |
Isolation |
1500 volts between field side and logic side |
|
500 volts between groups |
Output Current |
0.5 amps maximum per point |
|
2 amps maximum per common |
Output Characteristics |
|
Output Voltage Drop |
0.5 volts maximum |
Off-state Leakage |
1 mA maximum |
On Response Time |
2 ms maximum |
Off Response Time |
2 ms maximum |
Power Consumption |
110 mA (all outputs on) from 5 volt bus on backplane |
Picture/ Video Request
It's like having the store come to you!
Quick Quotes :
Receive price & availability FAST from our dedicated customer service team.Delivery :
Expedited, Freight, and International shipping available.
Warranty :
If there's a problem, we'll make it right. Your satisfaction is how we measure success!Returns :
No hassle return policy.Repair :
Our team of engineers are creative problem solvers who understand your challenges.Payment :
Custom Calibration :
You give us the specs and we do the rest.Share this page :
Tweet
Share
Share
Email Us