Brand/ Manufacturer:
General ElectricDimensions:
6.8x13.1cmx13.5cmWeight:
0.55 kgCountry of Origin: :
United StatesDescription:
Mark VI
Mfr. Part Number: |
IC695ALG600 |
|
|
Manufacturer: |
General Electric |
|
|
Description: |
IC693PWR330 PLCs/Machine Control from FANUC In Stock
|
|
|
Contact Details: |
E-mail:plcsale@mooreplc.com Skype:dddemi33 Whatsapp/Wechat:+86 18030235313 Manager: Tiffany
|
|
|
Status: |
Hope we can do more business soon ! There will become your honest cooperation partners!
Module Type: Universal Analog
Number of Inputs: 8 general purpose
Internal Power: 3.3V: 350mA; 5V: 400 mA
Number of Slots: 1 (single slot)
Range (ohms): 0 to 250/500/1000/2000/3000/4000
Power Dissapation: 5.4W max
The IC695ALG600 Thermocouple Input Module is a universal analog input module manufactured by GE Fanuc. It has 8 general-purpose input channels and 2 CJC channels. All the inputs are divided into 2 equal groups.
The IC695ALG600 Thermocouple Input Module offers 6 analog to digital filter frequencies which can be individually configured to each channel. Its diagnostic facilities have on-board error checking, open-circuit detection, short-circuit detection, and module fault reporting.
Some of the features of the module include full auto-calibration, on-board error checking, user-defined scaling, module fault reporting, terminal block insertion or removal detection, configurable software filters, and configurable interrupts. It provides temperature readings in Celsius or Fahrenheit.
Open circuit detection time |
5 seconds max. Open circuit detection is available for all configurations except +/- 20mA current, 0-20mA current, and +/-10V voltage. |
Max Overvoltage |
+/-14.5VDC continuous |
Max Overcurrent |
28 mA continuous |
Normal Mode Noise Rejection |
95 dB minimum @ 50/60 Hz with 8 Hz filter 85 dB minimum @ 50/60 Hz with 12 Hz filter |
Common Mode Noise Rejection |
120dB minimum @ 50/60 Hz with 8 Hz filter 110dB minimum @ 50/60 Hz with 12 Hz filter |
Settling time to 5% of Full Scale (notch filter dependent) |
<80 mS |
Calibrated Accuracy at 25°C |
Better than 0.1% of range (except 10 ohm CU RTD) Accuracy depends on A/D filter, data format, input noise, and ambient temperature. |
Calibration interval |
12 months typical to meet accuracy specifications over time. Module will allow for user offset to be applied as a periodic calibration adjustment. |
Input Offset Drift with Temperature |
3.0 milliohm/°C maximum 2.0 uV/°C maximum |
Gain Drift with Temperature |
50 ppm/°C typical (90 ppm/°C maximum) |
Module error over Full Temp range |
0.5% of range typical (depends on range) 1.0% of range maximum |
Module Scan Time (notch filter dependent) |
(Assumes 2 ADC’s running in parallel, no CJC or lead resistance) 10 ms per Channel × 4 Channels = 40 ms (1K Hz filter) 127 ms per Channel × 4 Channels = 508 ms (8 Hz filter) Channels that are disabled are not scanned, shortening scan time. |
Module conversion method |
Sigma-delta |
Isolation Voltage channel to channel group to group terminal block to backplane/chassis |
Opto-isolated, transformer isolated +-12.5Vdc channel to channel Tc/V/I/RTD 250 VAC continuous/1500 VAC for 60 seconds 250 VAC continuous/1500 VAC for 60 seconds |
Picture/ Video Request