Brand/ Manufacturer:
General ElectricDimensions:
3.5cmx13.5cmx13.5cmWeight:
0.26 kgCountry of Origin: :
United StatesDescription:
Analog Output HART
Mfr. Part Number: |
IC695ALG728 |
|
|
Manufacturer: |
General Electric |
|
|
Description: |
IC695ALG728 PACSystems RX3i Analog Output I/O module
|
|
|
Contact Details: |
E-mail:plcsale@mooreplc.com Skype:dddemi33 Whatsapp/Wechat:+86 18030235313 Manager: Tiffany
|
|
|
Status: |
Hope we can do more business soon ! There will become your honest cooperation partners!
No. of channels: 8
Voltage Range: 0 to +10 V, -10 to +10 V
Current Range: 0-20 mA, 4-20 mA
Update Rate: 8 msec
Output Load: 850 Ohms max
Power Consumption: 375 mA @ +3.3VDC, 315 mA @ +24VDC Isolate
The IC695ALG728 for the Rx3i is a Non-Isolated Analog Voltage/Current Output module for the Rx3i which provides 8 configurable voltage or current output channels with HART version 5.0 communications capability on each channel. The IC695ALG728 for the Rx3i module has two internal HART modems. Four single-ended channels are multiplexed with each HART modem.
The IC695ALG728 is an 8-Channel, Non-Isolated, Voltage/Current, HART, Analog Output module from the GE Fanuc RX3i Series. This module provides 8 configurable voltage or current output channels with HART communications. The IC695ALG728 has 2 internal HART modems. See specifications for this unit on IC695ALG728's website page.
Open circuit detection time |
5 seconds max. Open circuit detection is available for all configurations except +/- 20mA current, 0-20mA current, and +/-10V voltage. |
Max Overvoltage |
+/-14.5VDC continuous |
Max Overcurrent |
28 mA continuous |
Normal Mode Noise Rejection |
95 dB minimum @ 50/60 Hz with 8 Hz filter 85 dB minimum @ 50/60 Hz with 12 Hz filter |
Common Mode Noise Rejection |
120dB minimum @ 50/60 Hz with 8 Hz filter 110dB minimum @ 50/60 Hz with 12 Hz filter |
Settling time to 5% of Full Scale (notch filter dependent) |
<80 mS |
Calibrated Accuracy at 25°C |
Better than 0.1% of range (except 10 ohm CU RTD) Accuracy depends on A/D filter, data format, input noise, and ambient temperature. |
Calibration interval |
12 months typical to meet accuracy specifications over time. Module will allow for user offset to be applied as a periodic calibration adjustment. |
Input Offset Drift with Temperature |
3.0 milliohm/°C maximum 2.0 uV/°C maximum |
Gain Drift with Temperature |
50 ppm/°C typical (90 ppm/°C maximum) |
Module error over Full Temp range |
0.5% of range typical (depends on range) 1.0% of range maximum |
Module Scan Time (notch filter dependent) |
(Assumes 2 ADC’s running in parallel, no CJC or lead resistance) 10 ms per Channel × 4 Channels = 40 ms (1K Hz filter) 127 ms per Channel × 4 Channels = 508 ms (8 Hz filter) Channels that are disabled are not scanned, shortening scan time. |
Module conversion method |
Sigma-delta |
Isolation Voltage channel to channel group to group terminal block to backplane/chassis |
Opto-isolated, transformer isolated +-12.5Vdc channel to channel Tc/V/I/RTD 250 VAC continuous/1500 VAC for 60 seconds 250 VAC continuous/1500 VAC for 60 seconds |
Picture/ Video Request
It's like having the store come to you!